feat(modbus): add DDSU666 profile and select read function code per profile
- Add CHINT DDSU666 profile (ddsu666.yaml): FC03 holding registers, voltage/ current/active power (kW)/reactive power (kvar)/PF/frequency, import+export active energy. Word/byte order left at big-endian as a documented best guess (manual has no float example) — to be confirmed on-device. - Add DDSU666-Modbus-Protocol.md reference extracted from the official manual, plus the source PDF (parity with the SDM120 reference). - Generalize driver.read_blocks to dispatch FC03 (holding) or FC04 (input) based on a function_code argument (default 4, SDM120 behaviour unchanged); the code is validated before any connection is attempted. - Wire profile.function_code through the CLI read command, the background poller, and the device /test endpoint — previously the profile field was declared but never honoured (read path was hardcoded to FC04). - Tests: default -> FC04, function_code=3 -> FC03 holding, invalid FC rejected before connecting.
This commit is contained in:
Binary file not shown.
@@ -0,0 +1,198 @@
|
||||
# DDSU666 Modbus 协议(从官方 PDF 提取)
|
||||
|
||||
> 来源:`docs/references/DDSU666 Single phase Smart Meter.pdf`
|
||||
> (CHINT / 正泰仪表 **DDSU666 Single phase Smart Meter — Operation Manual**,文档号 `ZTY0.464.1224`,版本 **V2**,2020 年 8 月;厂商 Zhejiang Chint Instrument & Meter Co., Ltd.)
|
||||
> 本文件是 PDF 的可读化提取,供本项目的 Modbus 采集驱动设计参考。**以官方 PDF 为准**,本文件如有出入以 PDF 为准。
|
||||
> 同类文档见 SDM120 的 `SDM120-Modbus-Protocol.md`;两表差异较大,见下方 §6「与 SDM120 的关键差异」。
|
||||
|
||||
## 设备速览(来自手册 Table 1 / Table 5)
|
||||
|
||||
| 项 | DDSU666(直接接入) | DDSU666-CT(经互感器) |
|
||||
| --- | --- | --- |
|
||||
| 精度等级 | Active Class B | Active Class C |
|
||||
| 参考电压 | 230 V | 230 V |
|
||||
| 电流规格 | 0.25–5(80) A | 0.015–1.5(6) A |
|
||||
| 表常数 | 800 imp/kWh | 6400 imp/kWh |
|
||||
| 接入方式 | 直接接入 | 经电流互感器 |
|
||||
|
||||
- 单相电子式电能表,DIN35mm 导轨安装;测量电压、电流、有功/无功功率、频率、功率因数、正/反向有功电能。
|
||||
- 电能测量范围 `0~999999.99 kWh`(LCD 只显示 6 位,自动移动小数点)。
|
||||
- 通信:RS485,**Modbus-RTU**(也支持 DL/T 645-2007,可切换,见 §5 `0005H ChangeProtocol`)。
|
||||
- 手册 Table 1 标注 Frequency Reference = 60Hz,但 LCD 示例又写 `F=50.00Hz`(手册自身不一致);**实际频率以寄存器 `200EH` 读数为准**,不要把 50/60 写死。
|
||||
|
||||
## 0. 本项目的接入方式(重要)
|
||||
|
||||
DDSU666 物理层是 **Modbus RTU(RS-485 串口)**,半双工。和 SDM120 一样,本项目通过一个 **Modbus-TCP 网关**接入:
|
||||
|
||||
- 后端用 **Modbus TCP**(`IP:port`)连到网关,网关在串口侧转成 RTU 与电表通信。
|
||||
- TCP 帧用 MBAP header、**无 CRC**(CRC 由网关在 RTU 侧处理)。本文档里 RTU 帧的 `CRC (Lo/Hi)` 字段在 TCP 模式下不需要我们关心。
|
||||
- **Slave Address / Unit ID = 电表的通信地址 Addr**(范围 1–247;面板按键只能设 1–99;见 §5 `0006H`),在 TCP 请求里作为 unit id 传入。
|
||||
- 若以后直连串口(RTU),才需要管波特率 / 数据格式 / CRC:**默认串口格式是 8 数据位、无校验、2 停止位(8N2)**,与 SDM120 的 8N1 不同——直连时务必对齐。
|
||||
- 电表必须处于 **Modbus 协议模式**(而非 DL/T 645)才能用本协议;可经面板长按切换,或写 `0005H = 2`(见 §5)。
|
||||
|
||||
## 1. 协议帧格式(Appendix A)
|
||||
|
||||
异步传输,按字节为单位。一帧 10 位字符 = **1 起始位(0) + 8 数据位(无校验) + 2 停止位(1)**(其它格式可定制)。
|
||||
|
||||
### 信息帧结构(Table A.1)
|
||||
|
||||
| 字段 | 长度 | 说明 |
|
||||
| --- | --- | --- |
|
||||
| Start(起始) | >3.5 字符静默 | 帧间至少 3.5 字符空闲时间作为分隔 |
|
||||
| Address code(地址码) | 1 字节 | 目标从机地址 1–247;每个从机在总线上地址唯一 |
|
||||
| Function code(功能码) | 1 字节 | 仅支持 **03H / 10H**(见 §2) |
|
||||
| Data(数据域) | n 字节 | 随功能码不同而不同(起始地址、寄存器数、寄存器数据等) |
|
||||
| CRC check code(CRC 校验) | 2 字节 | 16-bit CRC(**低字节在前、高字节在后**;多项式 `A001`) |
|
||||
| End(结束) | >3.5 字符静默 | 帧间静默 |
|
||||
|
||||
> TCP 网关模式下 Start/End 静默与 CRC 由网关处理,本项目不关心。
|
||||
|
||||
### 功能码 03H 示例(读寄存器,Table A.3/A.4)
|
||||
|
||||
读从机 `01H`、起始地址 `0CH`、2 个寄存器:
|
||||
|
||||
- 主机发送:`01 03 00 0C 00 02 04 08`(最后 `04 08` 是 CRC,低字节 `04` 在前)。
|
||||
- 从机返回(设 `0CH/0DH` 内容为 `0000H`、`1388H`):`01 03 04 00 00 13 88 F7 65`
|
||||
- `04` = 字节数;`00 00` = `0CH` 数据;`13 88` = `0DH` 数据;`F7 65` = CRC(低字节 `F7` 在前)。
|
||||
|
||||
> **注意**:单个 16-bit 寄存器内是「高字节在前、低字节在后」(Table A.4 里 `0DH` 数据返回 `13 88` = `0x1388`)。这一点对解码浮点的字节序很关键,见 §3。
|
||||
|
||||
### 功能码 10H 示例(写多个寄存器,Table A.5/A.6)
|
||||
|
||||
向从机 `01H`、起始地址 `00H` 连续写 3 个寄存器 `0002H,1388H,000AH`:
|
||||
|
||||
- 主机发送:`01 10 00 00 00 03 06 00 02 13 88 00 0A 9B E9`
|
||||
- `06` = 写入字节数(3 寄存器 × 2 字节);随后是 3 个寄存器的数据;末尾 `9B E9` CRC。
|
||||
- 从机返回:`01 10 00 00 00 03 80 08`(回显起始地址 + 寄存器数 + CRC `80 08`)。
|
||||
|
||||
### 异常响应(Table A.7/A.8)
|
||||
|
||||
- 异常时返回的 Function Code = **原功能码 + 128**(即最高位置 1,`03H→83H`、`10H→90H`)。
|
||||
- 数据为单字节 Error Code:
|
||||
|
||||
| Error Code | 含义 | 说明 |
|
||||
| --- | --- | --- |
|
||||
| `01H` | Illegal function code | 收到的功能码本表不支持 |
|
||||
| `02H` | Illegal register address | 寄存器地址超出有效范围 |
|
||||
| `03H` | Illegal data value | 数据值超出对应地址的取值范围 |
|
||||
|
||||
## 2. 功能码
|
||||
|
||||
DDSU666 **只支持两个功能码**(Table A.2):
|
||||
|
||||
| 功能码 | 作用 | 说明 |
|
||||
| --- | --- | --- |
|
||||
| **03H** | Read register(读寄存器) | 读一个或多个寄存器——**测量值、电量、配置全部走它** |
|
||||
| **10H** | Write multiple registers(写多个寄存器) | 向 n 个连续寄存器写 n 个 16-bit 数据(改配置 / 清电量) |
|
||||
|
||||
> ⚠️ **DDSU666 没有「输入寄存器 / FC04」概念**——所有数据(包括电压电流功率)都用 **FC 03H** 读保持寄存器。这是它和 SDM120(测量值走 FC04)最大的踩坑差异,见 §6。
|
||||
|
||||
## 3. 数据编码
|
||||
|
||||
DDSU666 有两类数据:
|
||||
|
||||
1. **配置 / 参数寄存器(§5,`0000H`–`0010H`)**:每个 1 个寄存器、`16-bit with symbols`(**16 位有符号整数**)。
|
||||
2. **测量 / 电量寄存器(§4,`2000H`+ / `4000H`+)**:每个参数 = **32-bit IEEE-754 单精度浮点**(手册写 “single precision floating decimal”),占 **2 个相邻寄存器**(Length = 2 Word)。
|
||||
|
||||
**浮点字节序 / 字序**
|
||||
|
||||
- **字节序(byte order)= 大端:寄存器内高字节在前** —— 由 Table A.4 的 `0x1388` 返回为 `13 88` 确认。
|
||||
- **字序(word order,两个寄存器谁是高 16 位)**:手册**没有给出浮点解码的实例**,未明确标注。按标准 Modbus 浮点惯例应为**大端字序(高寄存器在前,`ABCD`)**,与本项目 SDM120 驱动一致(`registers_to_float` 用 `>f`,高寄存器在前)。
|
||||
- ⚠️ **需上机实测确认**:读 `2000H`(电压)应解出 ~230V 这样的合理值;若解出乱数,多半是字序相反,改成「低寄存器在前」再试。CHINT 同系列(DTSU/DDSU666)现场固件偶有字序差异,**首次接入务必用一个已知量(电压)校验**,不要凭手册想当然。
|
||||
|
||||
> Python 解码(大端、高寄存器在前):`struct.unpack('>f', struct.pack('>HH', hi_reg, lo_reg))[0]`。
|
||||
> pymodbus:`BinaryPayloadDecoder.fromRegisters(regs, byteorder=Endian.BIG, wordorder=Endian.BIG)`。
|
||||
|
||||
## 4. 测量 / 电量寄存器表(FC 03H 读)
|
||||
|
||||
全部为只读、`Float`(32-bit),每项占 **2 个寄存器**。地址为 Modbus 协议原始地址(即帧里的 Start Register Address Hi/Lo),手册用十六进制。
|
||||
|
||||
### 4.1 瞬时量(“Electric quantity of the secondary side”,`2000H` 段)
|
||||
|
||||
| 地址(hex) | 参数 | 代号 | 单位 | 备注 |
|
||||
| --- | --- | --- | --- | --- |
|
||||
| `2000H` | 电压 Voltage | U | V | |
|
||||
| `2002H` | 电流 Current | I | A | |
|
||||
| `2004H` | 有功功率 Active power | P | **kW** | 手册标注 “the unit is KW”——**不是 W** |
|
||||
| `2006H` | 无功功率 Reactive power | Q | **kvar** | |
|
||||
| `2008H` | (保留 RESERVED) | — | — | 占 2 寄存器,跳过 |
|
||||
| `200AH` | 功率因数 Power factor | PF | — | 无量纲 |
|
||||
| `200CH` | (保留 RESERVED) | — | — | 占 2 寄存器,跳过 |
|
||||
| `200EH` | 频率 Frequency | Freq | Hz | |
|
||||
|
||||
### 4.2 电量(“Electrical data of the secondary side”,`4000H` 段)
|
||||
|
||||
| 地址(hex) | 参数 | 代号 | 单位 | 备注 |
|
||||
| --- | --- | --- | --- | --- |
|
||||
| `4000H` | 正向(导入)有功电能 Active in electricity | Ep | kWh | 正向 / forward active energy |
|
||||
| `400AH` | 反向(导出)有功电能 Reverse in electricity | -Ep | kWh | 反向 / reverse active energy |
|
||||
|
||||
> 手册里 `4000H` 与 `400AH` 之间(`4002H`–`4009H`)未列出,视为保留/未文档化。
|
||||
|
||||
**读取分块建议**
|
||||
|
||||
- 瞬时量:`2000H`–`200FH` 共 **16 个寄存器连续**,一次块读即可覆盖 U…Freq(含两段 RESERVED,解码时跳过)。
|
||||
- 电量:`4000H`(2 寄存器)与 `400AH`(2 寄存器)相距较远,分两小块读,或读 `4000H`–`400BH`(12 寄存器)一次取出后挑用——以网关 / 电表是否允许跨保留地址块读为准,谨慎起见分开读更稳。
|
||||
|
||||
### 常用核心子集(日常监控够用)
|
||||
|
||||
电压 `2000H`、电流 `2002H`、有功功率 `2004H`(kW)、功率因数 `200AH`、频率 `200EH`、正向有功电能 `4000H`、反向有功电能 `400AH`。
|
||||
|
||||
## 5. 配置 / 参数寄存器表(FC 03H 读 / FC 10H 写)(Table 9)
|
||||
|
||||
每个 1 个寄存器、**16-bit 有符号整数**。`R/W` 列来自手册。
|
||||
|
||||
| 地址(hex) | 代号 | 含义 | R/W | 取值 / 说明 |
|
||||
| --- | --- | --- | --- | --- |
|
||||
| `0000H` | UCode | 编程密码 Programming password code | R/W | 写配置前的密码字 |
|
||||
| `0001H` | REV. | 保留;**实际读出的是版本号** | R | |
|
||||
| `0002H` | ClrE | 电能清零 CLr.E | R/W | **写 `1` 清除总电量**(不可逆,慎用) |
|
||||
| `0003H`–`0004H` | RESERVED | 保留 | — | |
|
||||
| `0005H` | ChangeProtocol | 协议切换 | R/W | **`2` = Modbus-RTU**,`1` = DL/T 645-2007 |
|
||||
| `0006H` | Addr | 通信地址 | R/W | 1–247(面板按键仅 1–99) |
|
||||
| `0007H`–`000AH` | RESERVED | 保留 | — | |
|
||||
| `000BH` | Meter type | 表型 Meter type | R | 只读设备类型标识 |
|
||||
| `000CH` | BAud | 通信波特率 | R/W | **`1`=2400bps,`2`=4800bps,`3`=9600bps**(手册寄存器仅列这三档;通信章另提到也支持 1200bps) |
|
||||
| `000DH`–`0010H` | RESERVED | 保留 | — | |
|
||||
|
||||
> ⚠️ 写 `0002H`(清电量)、`0006H`(改地址)、`000CH`(改波特率)、`0005H`(切协议)都会改变电表状态或通信参数,配错可能**清空累计电量**或**导致通信中断**。本项目默认**只读采集**,不在自动化链路里写电表配置寄存器。
|
||||
> 写配置通常需先经 `0000H UCode` 密码字校验;具体密码值手册正文未给出,需向厂商确认或经面板操作。
|
||||
|
||||
## 6. 与 SDM120 的关键差异(迁移 / 复用驱动时必看)
|
||||
|
||||
本项目已有 SDM120 profile(`app/integrations/modbus/profiles/sdm120.yaml`)。DDSU666 **不能照搬**,主要差异:
|
||||
|
||||
| 维度 | SDM120 (Eastron) | DDSU666 (CHINT) |
|
||||
| --- | --- | --- |
|
||||
| 读测量值功能码 | **FC 04**(输入寄存器 3X) | **FC 03**(保持寄存器,无 FC04) |
|
||||
| 测量值起始地址 | `0x0000` 起(30001) | 瞬时量 `0x2000` 起;电量 `0x4000`/`0x400A` |
|
||||
| 有功功率单位 | **W**(瓦) | **kW(千瓦)** —— 入库前注意换算 / 单位标注 |
|
||||
| 无功功率单位 | VAr | kvar |
|
||||
| 配置寄存器格式 | Float(FC03/16) | **16-bit 有符号整数**(FC03/10) |
|
||||
| 写功能码 | 16 / 0x10 | 10H(同 0x10) |
|
||||
| 串口默认格式 | 8N1(1 停止位) | **8N2(2 停止位)** |
|
||||
| 多协议 | 仅 Modbus | Modbus **与 DL/T 645-2007 可切换**(需确保在 Modbus 模式) |
|
||||
| 浮点字序 | 大端、高寄存器在前(手册有实例佐证) | 字节序大端已确认;**字序手册无实例,需上机实测** |
|
||||
|
||||
## 7. 给本项目采集驱动的要点小结
|
||||
|
||||
1. 走 **Modbus TCP 网关**:`ModbusTcpClient(host, port)`,`slave=<Addr>`;电表须在 **Modbus 协议模式**。
|
||||
2. 所有读取(测量 + 电量 + 配置)都用 **FC 03H**——**没有 FC04**。
|
||||
3. 测量值在 `0x2000` 段、电量在 `0x4000`/`0x400A`,均为 **float32**;解码大端字节序,**字序默认高寄存器在前但务必用电压实测校验**。
|
||||
4. **有功功率单位是 kW、无功是 kvar**——与 SDM120 的 W/VAr 不同,新建 profile / 入库映射时单位别抄错。
|
||||
5. 配置寄存器(`0x0000`–`0x0010`)是 **16-bit 有符号整数**,不是 float。
|
||||
6. 默认**只读**;`0002H` 写 1 会**清空累计电量**、`0006H/000CH/0005H` 会改通信参数,自动化链路里一律不写。
|
||||
7. 新建 profile 时这是 `ddsu666` 这一个 register profile 的定义;建议 `function_code: 3`、`word_order: big`(先按大端字序,接入后用电压读数验证)、瞬时量与电量分块读。
|
||||
|
||||
## 8. 实测记录(真机验证,2026-06-30)
|
||||
|
||||
首次接入一台 **DDSU666 直接接入版(5(80)A)** 实测,确认以下几点:
|
||||
|
||||
- **字序大端,确认无误**:电压 / 电流 / 频率 / 电能用「大端、高寄存器在前」解码全部得到合理值(如 233.9 V / 0.055 A / 49.99 Hz),与 §3 的假设一致。`ddsu666.yaml` 的 `word_order: big` / `byte_order: big` **无需修改**,§3 里「字序需上机实测」一项可视为已关闭。
|
||||
- **FC03 读通**:所有量走 FC03,profile `ddsu666` 在采集链路(CLI `read` / 设备 `/test` / 后台轮询)中工作正常。
|
||||
- **低电流下「瞬时功率读 0、但电能照常累加」**:测试负载仅为一台 PoE 交换机(≈230 V / 0.05 A,真实有功仅几瓦),**远低于本表测量量程下限 Imin≈0.25 A**。此工况下:
|
||||
- 瞬时 `active_power`(`0x2004`)与 `power_factor`(`0x200A`)寄存器返回**全零**(原始 hex `0x0000 0x0000`);电表 LCD 上功率在 0~3.3 W、PF 在 0~0.6 之间抖动。
|
||||
- 抖动成因 = **低电流测量噪声 + 开关电源(SMPS,无 PFC)畸变电流**(电流为电压峰值附近的窄脉冲、谐波重 → 畸变功率因数天然偏低)。**不是**「采样率与开关频率拍频」:计量芯片 SH79F7019 采样在 kHz 量级,远低于开关电源 50–200 kHz 的开关频率,两者不在一个频段。
|
||||
- 但累计电能 `import_energy`(`0x4000`)**正常累加**(实测 0 → 0.01 kWh)——电表内部积分器在防潜动起始电流(`0.004·Ib`≈0.02 A)之上照常计量。
|
||||
- **结论**:低于量程下限时**瞬时功率 / PF 不可信,但电能计量不丢**;电流进入量程(正常负载)后瞬时量即稳定可信。这是 5(80)A 大量程表对极小负载的固有特性,**非缺陷、非解码问题**。
|
||||
- **排错提示**:若日后看到 DDSU666「功率一直 0」,先确认负载电流是否在 Imin 以上——多半是负载太轻而非链路故障;可用 `scripts/modbus_cli probe --fc 3 --address 0x2000 --count 16` 看 `0x2004/0x2005` 原始寄存器是否真为全零佐证。
|
||||
Reference in New Issue