"""Modbus TCP driver — thin wrapper around pymodbus.
|
|
|
|
|
|
|
|
|
|
This module provides a single public function ``read_blocks`` that performs
|
2026-06-29 18:20:35 +02:00
|
|
|
one or more block reads against a Modbus TCP gateway — using either FC04
|
|
|
|
|
(Read Input Registers) or FC03 (Read Holding Registers), selected per call
|
|
|
|
|
via the ``function_code`` argument — and returns a flat
|
|
|
|
|
``dict[register_address -> 16-bit_value]`` map. The function code comes from
|
|
|
|
|
the device profile (e.g. SDM120 uses FC04, DDSU666 uses FC03).
|
2026-06-22 13:03:50 +02:00
|
|
|
|
|
|
|
|
Design decisions
|
|
|
|
|
----------------
|
|
|
|
|
- **Only read function codes** (FC03/FC04) are exposed. There is no write path.
|
|
|
|
|
- float32 decoding uses ``struct.unpack('>f', ...)`` directly rather than the
|
|
|
|
|
pymodbus ``BinaryPayloadDecoder`` helper, which has had API churn across 3.x
|
|
|
|
|
releases. Big-endian word order + big-endian byte order means the 4 raw bytes
|
|
|
|
|
are already in standard network (big-endian) order.
|
|
|
|
|
- ``ModbusTcpClient`` is used in synchronous mode (``connect()`` / ``close()``).
|
|
|
|
|
The client is created fresh per call; this keeps the driver stateless and
|
|
|
|
|
avoids threading concerns at the cost of one TCP handshake per read cycle.
|
|
|
|
|
APScheduler jobs call this from a thread pool, so stateless is safer.
|
|
|
|
|
- pymodbus 3.13.x uses ``device_id=`` as the slave-address keyword argument
|
|
|
|
|
(renamed from ``slave=`` in earlier 3.x releases).
|
|
|
|
|
|
|
|
|
|
Exceptions
|
|
|
|
|
----------
|
|
|
|
|
``ModbusDriverError``
|
|
|
|
|
Base exception for all driver-level errors.
|
|
|
|
|
``ModbusConnectionError``
|
|
|
|
|
Raised when the TCP connection to the gateway cannot be established or is
|
|
|
|
|
lost during the read.
|
|
|
|
|
``ModbusResponseError``
|
|
|
|
|
Raised when the gateway responds with a Modbus exception frame or when the
|
|
|
|
|
returned register count does not match the requested count.
|
|
|
|
|
"""
|
|
|
|
|
|
|
|
|
|
from __future__ import annotations
|
|
|
|
|
|
|
|
|
|
import logging
|
|
|
|
|
import struct
|
|
|
|
|
from typing import TYPE_CHECKING
|
|
|
|
|
|
|
|
|
|
from pymodbus.client import ModbusTcpClient
|
|
|
|
|
from pymodbus.exceptions import ConnectionException, ModbusException
|
|
|
|
|
|
|
|
|
|
if TYPE_CHECKING:
|
|
|
|
|
from collections.abc import Sequence
|
|
|
|
|
|
|
|
|
|
logger = logging.getLogger(__name__)
|
|
|
|
|
|
|
|
|
|
# ---------------------------------------------------------------------------
|
|
|
|
|
# Custom exceptions
|
|
|
|
|
# ---------------------------------------------------------------------------
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
class ModbusDriverError(RuntimeError):
|
|
|
|
|
"""Base class for all Modbus driver errors."""
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
class ModbusConnectionError(ModbusDriverError):
|
|
|
|
|
"""Cannot connect to (or lost connection with) the Modbus TCP gateway."""
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
class ModbusResponseError(ModbusDriverError):
|
|
|
|
|
"""Modbus gateway returned an exception frame or an unexpected response."""
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
# ---------------------------------------------------------------------------
|
|
|
|
|
# Block definition type alias
|
|
|
|
|
# ---------------------------------------------------------------------------
|
|
|
|
|
|
|
|
|
|
#: A single read block: ``{"start": int, "count": int}``.
|
|
|
|
|
Block = dict[str, int]
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
# ---------------------------------------------------------------------------
|
|
|
|
|
# Public API
|
|
|
|
|
# ---------------------------------------------------------------------------
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
def read_blocks(
|
|
|
|
|
host: str,
|
|
|
|
|
port: int,
|
|
|
|
|
unit_id: int,
|
|
|
|
|
blocks: Sequence[Block],
|
|
|
|
|
*,
|
2026-06-29 18:20:35 +02:00
|
|
|
function_code: int = 4,
|
2026-06-22 13:03:50 +02:00
|
|
|
timeout: float = 3.0,
|
|
|
|
|
) -> dict[int, int]:
|
2026-06-29 18:20:35 +02:00
|
|
|
"""Read one or more contiguous register blocks via FC03 or FC04.
|
2026-06-22 13:03:50 +02:00
|
|
|
|
|
|
|
|
Parameters
|
|
|
|
|
----------
|
|
|
|
|
host:
|
|
|
|
|
Hostname or IP address of the Modbus TCP gateway.
|
|
|
|
|
port:
|
|
|
|
|
TCP port (typically 502).
|
|
|
|
|
unit_id:
|
|
|
|
|
Modbus slave / unit address (the device's Meter ID for SDM120).
|
|
|
|
|
blocks:
|
|
|
|
|
Sequence of ``{"start": int, "count": int}`` dicts describing the
|
|
|
|
|
contiguous register ranges to read. ``count`` is the number of
|
|
|
|
|
16-bit registers (not bytes).
|
2026-06-29 18:20:35 +02:00
|
|
|
function_code:
|
|
|
|
|
Modbus read function code: ``4`` for FC04 (Read Input Registers,
|
|
|
|
|
default — SDM120) or ``3`` for FC03 (Read Holding Registers —
|
|
|
|
|
DDSU666 and other devices that expose measurements as holding
|
|
|
|
|
registers). Comes from the device profile's ``function_code`` field.
|
2026-06-22 13:03:50 +02:00
|
|
|
timeout:
|
|
|
|
|
TCP connect/read timeout in seconds (default 3 s).
|
|
|
|
|
|
|
|
|
|
Returns
|
|
|
|
|
-------
|
|
|
|
|
dict[int, int]
|
|
|
|
|
Flat mapping of ``{register_address: 16-bit_register_value}`` for
|
|
|
|
|
every register returned across all blocks.
|
|
|
|
|
|
|
|
|
|
Raises
|
|
|
|
|
------
|
2026-06-29 18:20:35 +02:00
|
|
|
ModbusDriverError
|
|
|
|
|
If ``function_code`` is neither 3 nor 4 (validated before any
|
|
|
|
|
connection is attempted).
|
2026-06-22 13:03:50 +02:00
|
|
|
ModbusConnectionError
|
|
|
|
|
If the TCP connection to the gateway fails.
|
|
|
|
|
ModbusResponseError
|
|
|
|
|
If the gateway returns a Modbus exception frame or an unexpected
|
|
|
|
|
number of registers.
|
|
|
|
|
"""
|
2026-06-29 18:20:35 +02:00
|
|
|
if function_code not in (3, 4):
|
|
|
|
|
raise ModbusDriverError(
|
|
|
|
|
f"Unsupported read function code FC{function_code:02d} "
|
|
|
|
|
f"(only FC03 holding-register and FC04 input-register reads are supported)"
|
|
|
|
|
)
|
|
|
|
|
|
2026-06-22 13:03:50 +02:00
|
|
|
client = ModbusTcpClient(host, port=port, timeout=timeout)
|
|
|
|
|
try:
|
|
|
|
|
connected = client.connect()
|
|
|
|
|
if not connected:
|
|
|
|
|
raise ModbusConnectionError(
|
|
|
|
|
f"Could not connect to Modbus gateway at {host}:{port}"
|
|
|
|
|
)
|
|
|
|
|
|
|
|
|
|
registers: dict[int, int] = {}
|
|
|
|
|
for block in blocks:
|
|
|
|
|
start: int = block["start"]
|
|
|
|
|
count: int = block["count"]
|
2026-06-29 18:20:35 +02:00
|
|
|
_read_block(client, unit_id, start, count, registers, function_code=function_code)
|
2026-06-22 13:03:50 +02:00
|
|
|
|
|
|
|
|
return registers
|
|
|
|
|
|
|
|
|
|
except ConnectionException as exc:
|
|
|
|
|
raise ModbusConnectionError(
|
|
|
|
|
f"Connection to Modbus gateway {host}:{port} failed: {exc}"
|
|
|
|
|
) from exc
|
|
|
|
|
except ModbusException as exc:
|
|
|
|
|
raise ModbusResponseError(f"Modbus protocol error: {exc}") from exc
|
|
|
|
|
finally:
|
|
|
|
|
client.close()
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
def _read_block(
|
|
|
|
|
client: ModbusTcpClient,
|
|
|
|
|
unit_id: int,
|
|
|
|
|
start: int,
|
|
|
|
|
count: int,
|
|
|
|
|
result: dict[int, int],
|
2026-06-29 18:20:35 +02:00
|
|
|
*,
|
|
|
|
|
function_code: int,
|
2026-06-22 13:03:50 +02:00
|
|
|
) -> None:
|
2026-06-29 18:20:35 +02:00
|
|
|
"""Read one block and merge into *result*. Raises on any error.
|
|
|
|
|
|
|
|
|
|
``function_code`` is assumed already validated to be 3 or 4 by the caller
|
|
|
|
|
(``read_blocks``); 3 dispatches FC03 (holding) and 4 dispatches FC04 (input).
|
|
|
|
|
"""
|
2026-06-22 13:03:50 +02:00
|
|
|
try:
|
2026-06-29 18:20:35 +02:00
|
|
|
if function_code == 3:
|
|
|
|
|
response = client.read_holding_registers(start, count=count, device_id=unit_id)
|
|
|
|
|
else: # function_code == 4 (input registers)
|
|
|
|
|
response = client.read_input_registers(start, count=count, device_id=unit_id)
|
2026-06-22 13:03:50 +02:00
|
|
|
except ConnectionException as exc:
|
|
|
|
|
raise ModbusConnectionError(
|
|
|
|
|
f"Lost connection while reading registers 0x{start:04X}+{count}: {exc}"
|
|
|
|
|
) from exc
|
|
|
|
|
|
|
|
|
|
if response.isError():
|
|
|
|
|
raise ModbusResponseError(
|
|
|
|
|
f"Modbus exception reading registers 0x{start:04X}+{count}: {response}"
|
|
|
|
|
)
|
|
|
|
|
|
|
|
|
|
regs = response.registers
|
|
|
|
|
if len(regs) != count:
|
|
|
|
|
raise ModbusResponseError(
|
|
|
|
|
f"Expected {count} registers from 0x{start:04X}, got {len(regs)}"
|
|
|
|
|
)
|
|
|
|
|
|
|
|
|
|
for offset, value in enumerate(regs):
|
|
|
|
|
result[start + offset] = value
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
# ---------------------------------------------------------------------------
|
|
|
|
|
# Decoding helpers
|
|
|
|
|
# ---------------------------------------------------------------------------
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
def registers_to_float(hi_reg: int, lo_reg: int) -> float:
|
|
|
|
|
"""Decode two 16-bit registers to a big-endian IEEE-754 float32.
|
|
|
|
|
|
|
|
|
|
The SDM120 (and most Modbus float devices) use big-endian word order:
|
|
|
|
|
the high 16-bit register comes first, then the low register. Combined
|
|
|
|
|
with big-endian byte order within each register, the raw 4-byte sequence
|
|
|
|
|
is standard network-byte-order (big-endian) float32.
|
|
|
|
|
|
|
|
|
|
Parameters
|
|
|
|
|
----------
|
|
|
|
|
hi_reg:
|
|
|
|
|
The first (higher-address-range, most-significant) 16-bit register.
|
|
|
|
|
lo_reg:
|
|
|
|
|
The second (lower-address-range, least-significant) 16-bit register.
|
|
|
|
|
|
|
|
|
|
Returns
|
|
|
|
|
-------
|
|
|
|
|
float
|
|
|
|
|
The decoded IEEE-754 single-precision floating-point value.
|
|
|
|
|
|
|
|
|
|
Example
|
|
|
|
|
-------
|
|
|
|
|
>>> registers_to_float(0x4366, 0x3334)
|
|
|
|
|
230.20001220703125
|
|
|
|
|
"""
|
|
|
|
|
raw = struct.pack(">HH", hi_reg, lo_reg)
|
|
|
|
|
return struct.unpack(">f", raw)[0]
|